Daikin · Furnace

EE8 High-stage pressure switch closed at start of heating cycle

Medium severity Daikin DR96TN/DD96TN

What the control is telling you

On a two-stage furnace the high-stage pressure switch circuit is already closed at the start of a heat call. The furnace runs on low stage only (inducer still operates). Flowcharts call this code E8.

Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready

Likely causes

  • High-stage pressure switch contacts stuck closed
  • Short in the pressure switch circuit wiring

Test and repair steps

  1. Power off, remove the wires from the high-stage pressure switch and ohm the contacts with the inducer off - they must be open.
  2. Replace the high-stage pressure switch if the contacts are closed with no vacuum.
  3. If the switch is good, find and repair the short in the switch wiring.
  4. Retest a high-fire call (W1+W2) and confirm the furnace stages up.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; Error Code E1, E2, E8, E9 flowchart p.36. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.