Carrier · Heat pump

99 High torque lockout

High severity Carrier Infinity 18VS 25VNA8

What the control is telling you

Amber STATUS light flashes 99. High torque kept happening on the lowest stage (elevated from code 98). 2-hour lockout. Type: System malfunction; reset: 2 hours.

Applies to: Carrier Infinity 18VS variable speed heat pump 25VNA8 (AOC control + inverter)

Likely causes

  • Cooling: Overcharged system
  • Heating: Overcharged system
  • Compressor leads miswired at U, V, W
  • Outdoor airflow too low or off
  • Expansion device restriction (TXV / EXV)

Test and repair steps

  1. Cooling check subcooling in Charging Mode (or the subcooling chart on the control box door) and adjust charge.
  2. Heating compare pressures with the heating check chart; if they do not match, recover, evacuate and weigh in the rating plate charge.
  3. Check compressor lead order at U, V, W.
  4. Check the outdoor coil and fan.
  5. Troubleshoot the TXV and EXV.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 25VNA8 / 24VNA9 Service Manual, Table 6 Fault Code Actions, p.26. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.