Carrier · Heat pump

95 Compressor over current lockout

High severity Carrier Infinity 18VS 25VNA8

What the control is telling you

Amber STATUS light flashes 95. Compressor current kept going too high (elevated from code 49). 2-hour lockout. Type: System malfunction; reset: 2 hours.

Applies to: Carrier Infinity 18VS variable speed heat pump 25VNA8 (AOC control + inverter)

Likely causes

  • Cooling: Outdoor airflow too low or off
  • High superheat - TXV / EXV problem
  • Compressor outside its operating range
  • Supply voltage outside the rating plate range
  • Loose or wrong wiring to the compressor
  • Phase imbalance / leads miswired
  • Refrigerant overcharge
  • Damaged inverter or compressor

Test and repair steps

  1. Check the outdoor coil and fan.
  2. Troubleshoot TXV and EXV; check the suction pressure transducer and suction sensor.
  3. Check supply voltage against the rating plate and all power / compressor plug connections.
  4. Measure compressor winding resistance (between terminals: about 1.13 ohm sizes 13/24B, 0.59 sizes 25/36, 0.37 sizes 37/48, 0.24 sizes 49/60; over 1 megohm to ground - do not use a megger).
  5. Check the refrigerant charge.
  6. Replace the inverter, then the compressor, only after the above checks.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 25VNA8 / 24VNA9 Service Manual, Table 6 Fault Code Actions, p.25. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.