Carrier · Heat pump
61 Fan inverter fault
What the control is telling you
Amber STATUS light flashes 61. The outdoor fan motor failed to start or its rotor is out of position. After 5 occurrences it becomes code 76. Type: Local; reset: Automatic retry.
Applies to: Carrier Infinity 18VS variable speed heat pump 25VNA8 (AOC control + inverter)
Likely causes
- Fan motor failed to start
- Fan rotor misalignment
Test and repair steps
- Check the outdoor fan motor and blade turn freely and run.
- If it repeats, troubleshoot as code 76.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 25VNA8 / 24VNA9 Service Manual, Table 6 Fault Code Actions, p.21. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.