34.2 Flame lost before blower on-delay
What the control is telling you
Flame was proven after ignition but then lost before the heating blower on-delay ended.
Applies to: Carrier 59SC6A
Likely causes
- Dirty flame sensor
- Gas pressure drop after valve opens
- Vent or combustion air problem
- Poor ground
Test and repair steps
- Warning: Turn off gas and power and lock out before removing burner parts.
- Clean the flame sensor with 0000 steel wool only (no sandpaper or emery cloth); check it sits in the flame.
- Verify ground continuity green/yellow wire to gas valve and manifold bracket screw, and the flame-sense ground wire to furnace sheet metal.
- Check natural gas supply (4.5-14 in. w.c.) while burning and manifold pressure (2.8-3.8 in. w.c. for 40k-120k models; max 1.8 in. w.c. on 26k).
- Inspect burners and orifices for dirt or blockage; clean burner with brush and vacuum.
- Inspect vent and combustion-air pipes for water, sags or blockage.
- Run 2 complete heat cycles and look at the flame: it should be clear blue, almost transparent.
Settings for these units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59SC6A Installation, Start-up, Operating and Service Instructions, Fig. 60 Service Label p.54; Cleaning Burners and Flame Sensor p.66; Fig. 61 notes p.56. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.