33.1 Main limit circuit switch open
What the control is telling you
A switch in the main limit circuit (auto-reset limit or a manual-reset rollout switch) has opened.
Applies to: Carrier 59SC6A
Likely causes
- Restricted airflow (filter, ducts, registers)
- Airflow setting too low / high temperature rise
- Blower failure
- Over-firing
- Flame rollout from combustion air, gas pressure, burner or vent problem
Test and repair steps
- Warning: Never jumper the limit or flame rollout switches.
- Check and clean/replace the filter (it is external to the casing); open all registers and check ducts for restrictions.
- Measure temperature rise with the blower door on: duct thermometers in supply and return near the furnace, out of line-of-sight of the heat exchanger. It must be within the rating-plate range; midpoint or slightly above is recommended.
- If the rise is high, check gas input rate, altitude derate, and duct static; static above 0.50 in. w.c. is excessive.
- Raise the Ht heating airflow setting to lower the rise (lower it to raise the rise).
- Check manifold pressure for 40,000-120,000 BTUh models it must be 2.8-3.8 in. w.c. on natural gas; on the 26,000 BTUh model (green label on gas valve solenoid, Table 26) do not exceed 1.8 in. w.c.
- Check blower operation with the Ct component test; check the blower wheel and motor are clean.
- If a manual-reset flame rollout switch tripped, correct combustion air, gas pressure, burner/orifice position or venting before resetting it.
- Verify the limit works run the furnace at least 5 minutes, slowly block the return air until the limit trips, then unblock; burners should relight once it cools.
Settings for these units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59SC6A Installation, Start-up, Operating and Service Instructions, Fig. 60 Service Label p.54; Start-up caution p.55; Adjust Temperature Rise and Check Safety Controls p.58-61. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.