14 Ignition lockout

Critical severity 59TP6A58SB0A/58SB1A

What the control is telling you

The furnace failed to light and prove flame in 4 tries. Auto-resets after 3 hours.

Applies to: 59TP6A two-stage variable-speed ECM multipoise condensing gas furnace, all sizes (040-10 to 120-22)

Likely causes

  • Gas off or manual shutoff closed
  • Igniter, gas valve or flame sensor fault
  • Low inlet gas pressure
  • Poor ground / flame sensor grounded

Test and repair steps

  1. Warning: Shut off 115-V power and gas, and lock/tag out before working inside the furnace; there may be more than one power source.
  2. Follow the code 34 diagnostic steps; 14 is the lockout after 34 repeats.
  3. Confirm gas valve and manual shutoff are open.
  4. Reset by briefly cutting 115 V, or 24 V at SEC1/SEC2 (not at W/W1, G or R).
  5. Watch a full ignition cycle 15-second prepurge, 17-second igniter warm-up, gas valve opens, 2-second flame-proving period starting 5 seconds after the gas valve relay closes.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 59TP6A Installation, Start-up, Operating and Service Instructions, Fig. 66 Troubleshooting Guide, p.88; Sequence of Operation, p.85. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.