Carrier · Furnace
10.1 L1 polarity fault
What the control is telling you
The control sees reversed 115-V line/neutral polarity. The status LED flashes rapidly and the furnace will not operate.
Applies to: Carrier 59SC6A
Likely causes
- Hot and neutral reversed at the furnace junction box
- Reversed polarity in building wiring or power cord
- Poor or missing ground
Test and repair steps
- Warning: Turn off power at the disconnect before working in the junction box; verify with a meter.
- Confirm the LED is flashing rapidly and display shows 10.1.
- Measure voltage L1 (black) to ground should read about 115 V; neutral (white) to ground should read near 0 V.
- Correct reversed hot/neutral at the J-box or upstream source.
- Verify the furnace ground is continuous and the green/yellow ground to the gas valve and manifold bracket is intact; the control locks out if not grounded.
- Restore power and confirm the code clears and the furnace operates.
Settings for these units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59SC6A Installation, Start-up, Operating and Service Instructions, Fig. 60 Service Label p.54; 115-V Wiring and Start-up General p.55. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.