Carrier · Air conditioner
99 High torque lockout
What the control is telling you
Amber STATUS light flashes 99. High torque kept happening on the lowest stage (elevated from code 98). 2-hour lockout. Type: System malfunction; reset: 2 hours.
Applies to: Carrier Infinity 19VS variable speed air conditioner 24VNA9 (AOC control + inverter)
Likely causes
- Overcharged system
- Compressor leads miswired at U, V, W
- Outdoor airflow too low or off
- Expansion device restriction (TXV)
Test and repair steps
- Cooling check subcooling in Charging Mode (or the subcooling chart on the control box door) and adjust charge.
- Check compressor lead order at U, V, W.
- Check the outdoor coil and fan.
- Troubleshoot the TXV.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 25VNA8 / 24VNA9 Service Manual, Table 6 Fault Code Actions, p.26. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.