95 Compressor over current lockout
What the control is telling you
Amber STATUS light flashes 95. Compressor current kept going too high (elevated from code 49). 2-hour lockout. Type: System malfunction; reset: 2 hours.
Applies to: Carrier Infinity 19VS variable speed air conditioner 24VNA9 (AOC control + inverter)
Likely causes
- Outdoor airflow too low or off
- High superheat - TXV problem
- Compressor outside its operating range
- Supply voltage outside the rating plate range
- Loose or wrong wiring to the compressor
- Phase imbalance / leads miswired
- Refrigerant overcharge
- Damaged inverter or compressor
Test and repair steps
- Check the outdoor coil and fan.
- Troubleshoot TXV; check the suction pressure transducer and suction sensor.
- Check supply voltage against the rating plate and all power / compressor plug connections.
- Measure compressor winding resistance (between terminals: about 1.13 ohm sizes 13/24B, 0.59 sizes 25/36, 0.37 sizes 37/48, 0.24 sizes 49/60; over 1 megohm to ground - do not use a megger).
- Check the refrigerant charge.
- Replace the inverter, then the compressor, only after the above checks.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 25VNA8 / 24VNA9 Service Manual, Table 6 Fault Code Actions, p.25. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.