Carrier · Air conditioner
46 Brownout
What the control is telling you
Amber STATUS light flashes 46. Line voltage fell too low (under about 187 V for 4 s). Compressor and fan stop and stay off until voltage is back to at least 190 V. Type: Local; reset: 6 minutes.
Applies to: Carrier Infinity 19VS variable speed air conditioner 24VNA9 (AOC control + inverter)
Likely causes
- Low supply voltage
- Bad connection on L1 / L2
- Inverter not reading voltage correctly
Test and repair steps
- Measure line voltage at the unit; it should be above about 180-190 V. If it stays low, contact the utility.
- Check line and load side connections on L1 and L2.
- If voltage and connections are good, replace the inverter.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 25VNA8 / 24VNA9 Service Manual, Table 6 Fault Code Actions, p.19. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.