AirQuest · Furnace

33 Limit circuit fault

High severity

What the control is telling you

Main limit, rollout or auxiliary limit is open.

Applies to: Carrier/ICP-family two-digit status codes — confirm with the code label on the unit

Likely causes

  • Restricted airflow
  • Flame rollout
  • Faulty limit switch
  • Blower issue

Test and repair steps

  1. Check filter, blower and duct restrictions
  2. Check rollout switches — if tripped, inspect heat exchanger and venting before resetting
  3. Verify temperature rise
  4. Test limit switches for continuity when cool

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier/ICP status code label — verify per model. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.